Khuphela iPDF yezichazi zobuchwepheshe

Ukugcinwa kweBhetri yeLanga okuDityaniswe nge-AC xa kuthelekiswa nokuDityaniswe nge-DC kwi-PV yorhwebo esele ikho

I-MegSolid ESSA0100B-0215 kwisiza esele sikho se-PV sorhwebo, ebonisa iindlela zokufaka kwakhona ezidityaniswe kwi-AC nakwi-DC

Kwisikhululo sombane welanga sokurhweba esele sikho esine-inverter esisebenza kakuhle, Ugcino lwebhetri oludityaniswe ne-AC ludla ngokuba lolokuqala ulwakhiwo olufakelwa kwakhona oluvavanywayo., ukuba iswitshibhodi, itransfoma kunye ne-PCC zingakwazi ukwamkela i-PCS yebhetri eyongezelelweyo. Ukuqhagamshelwa kwe-DC kuyenyuka xa sele kucwangcisiwe ukuvuselelwa kwamandla e-PV, i-clipping elinganisekayo inexabiso elinokubuyiswa, okanye imigaqo yasekuhlaleni yokuqhagamshela i-grid ixhasa isikhululo esinye esidibeneyo selanga kunye nogcino-bhetri.

I-Coupling topology ayimisi ubungakanani bebhetri. Amandla e-PCS afunekayo kunye namandla ebhetri zivela kumthwalo wendawo, ixesha lokukhupha umbane kunye nomthwalo wokusebenza; isigqibo se-AC/DC simisela indlela olu gcino olusebenzisana ngayo nesikhululo se-PV. La manyathelo oyilo ahlukeneyo aqukwe kwi Isikhokelo soyilo se-C&I BESS, Isikhokelo somlinganiselo wamandla-ukuya-kwi-amandla e-BESS kwaye Isikhokelo soqhagamshelo lwe-400 V BESS.

Kwiprojekthi yendawo esele isetyenzisiwe, uyilo kufuneka lungenelele yonke inxalenye yesikhululo samandla elanga elinyanzela i-EPC ukuba isivule kwakhona. Amanqanaba ambalwa okuguqula amandla elanga ukuya kwibhetri abalulekile kuphela xa amandla afunyenweyo okanye inzuzo yokusebenza idlula iindleko zezixhobo ezitshintshiweyo, ixesha elongezelelweyo lokuvala, kunye nomsebenzi ohlaziyiweyo wokukhusela nowolawulo.

Qala ngefama yamandla elanga esele ikhona, hayi ibhetri.

Uhlaziyo lwe-PV lwezorhwebo kufuneka luqale ngesixhobo esele sinika ixabiso kwindawo. Phambi kokuthelekisa ukugcinwa kwebhetri okudityaniswe kwi-AC kunye nokudityaniswe kwi-DC, sima yintoni enokuhlala, yintoni esele kufuneka itshintshwe, kunye nomda wombane ekufuneka i-BESS entsha isebenze kuwo..

Qala ngokujongaIsizathu sokuba isakhiwo sinokutshintsha
Imodeli ye-inverter ye-PV kunye ne-firmwareIyachonga ii-interface ezikhoyo kunye nobuchule bokulawula
Umhla wokugunyazisaIbonisa ukuba kusele ixesha elingakanani lobomi benkonzo
Iwaranti eseleyoUkutshintshwa kunokuphelisa ixabiso lewaranti.
Iphleyiti yegama ye-PV DCSimisa ubungakanani boluhlu
Umgangatho we-Inverter ACImisela umda wangoku wokuguqulwa kwe-AC.
Imitya kunye nokwabiwa kwe-MPPTIbonisa ukuba uhlaziyo luya kufuna ukulungiswa ngokutsha okungakanani kwicala le-DC.
Idatha yemveliso ye-PVIbonisa xa amandla elanga asetyenziswayo efumanekayo
Iinkcukacha zomthwalo wesizaIbonisa xa ukugqithisa kwamandla e-PV kunye nemfuno yebhetri ngokwenene zihambelana.
I-PCC nomda wokuthumela ngaphandleIchaza umda wamandla ajongene negridi
I-transformer neswitshibhodiIjonga ukuba i-PCS yebhetri eyahlukileyo ingongezwa na.

Sebenzisa idatha yokusebenza elungelelanisiweyo endaweni yamanani apheleleyo omveliso wonyanga. I-kWh yonyaka ayinakubonisa ukuba ibhetri ibiya kuba namandla okutshajwa na xa kwenzeka isiganeko esijoliswe kuso sokusebenza.

Ubudala be-inverter butshintsha umlinganiselo weendleko kwangoko. I-inverter exhaswayo eyafakwa kwiminyaka emithathu eyadlulayo isenobomi obusebenzisekayo kwaye mhlawumbi isenexabiso lewaranti. Iyunithi eneminyaka elishumi elinanye esele idweliswe ukuba itshintshwe yahlukile: iindleko ze-inverter ethile, zokhuseleko, kunye nokuyifaka kwakhona sele ziyinxalenye yohlahlo-lwabiwo-mali lwendawo lokutsha amandla.

Ukudityaniswa kwe-AC ne-DC kuchaza kuphela indawo yokudibana kumbane.

Ukudibanisa kuchaza Apho iindlela zamandla e-PV nebhetri zidibana khona. Ayimisi ngokwayo umlinganiselo webhetri we-kWh, isakhono sokugcina umbane okanye ukusebenza kolawulo lokuthumela ngaphandle.

Indlela edityaniswe nge-AC

Iindlela eziphambili zamandla zezi:

Indlela edityaniswe nge-DC

Ubunjineli bezakhiwoIsiphumo esiphambili sokulungiswa kwakhona
Edityaniswe nge-ACIgcina inxalenye enkulu yohlelo lwe-PV DC esele lukho, kodwa yongeza omnye i-AC converter.
Idityaniswe nge-DCIdibanisa i-PV nebhetri ngokusondeleyo, kodwa inokuvula kwakhona uyilo lokhuseleko lwe-voltage, i-MPPT, i-current kunye ne-DC.

Akufanelanga kuthiwe ibhetri iyahambelana neendawo zokufaka zombane ze-DC ze-inverter esele ikhona edityaniswe kwigridi. Iifestile zovoltage, umsinga, ulwabiwo lwe-MPPT, ukhuseleko, ukwahlulwa kunye nolawulo lwe-converter zonke zifuna ukuqinisekiswa.

Umzobo uthelekisa iindawo zokudibana zombane zeebhetri zelanga ezidityaniswe nge-AC nezezo zidityaniswe nge-DC kwibhasi ye-AC nakwibhasi ye-DC.

Ufakelo kunye nokuthunyelwa kunokuguqula ukhetho olucacileyo lwezakhiwo.

“I-PV esele ikhona ithanda i-AC; i-solar-plus-storage entsha ithanda i-DC” yimbono yokuqala kuphela. Iingqikelelo zokuthunyelwa zombane ezisekelwe kwimeko yokwenyani zinokutshintsha ubungakanani be-BESS, uqoqosho lweprojekthi kunye nesakhiwo esikhethwayo. imagazini ye-PV

Umsebenzi ophambiliUmbuzo wezakhiwo ekufuneka usonjululwe
Ukucheba incophoIngaba i-BESS ingakwazi ukuthumela ngokuzimeleyo ngokuchasene nesilindelo se-PCC?
Ukusetyenziswa kwelanga ngokwakhoLingakanani i-PV eseleyo xa ibhetri iyakwazi ukutshaja?
Ukuchacha kokusikaIngaba isitoreji singakwazi ukufikelela kumandla angaphezulu komda we-inverter okhoyo?
I-arbitrage yegridiKuza kuba rhoqo kangakanani ukuba i-charger ifumane umbane kwigridi?
Ulawulo lwe-exportYeyiphi i-controller kunye ne-actuator ezinyanzelisa usukelo lwe-PCC?
Ukuthunyelwa okuxubeneyoYeyiphi imida eqhelekileyo ethintela i-PV + BESS?
Ugcino-mbuyiseloYimalini ye-SOC ekufuneka igcinwe?
Iinkonzo zegridiIngaba i-PCS kunye nendlela yokudibanisa ziyayixhasa na le ndima?

Qandisa itheyibhile yokusebenza phambi kokukhetha itopoloji:

Indlela → Umthombo wokutshaja → Indawo yokukhupha i-charge → Iifestile ze-SOC → Umda wamandla → Ijelo le-PCC

Isigqibo Sokuqala Sezorhwebo: Gcina okanye Tshintsha i-Inverter ye-PV Ekhoyo

Phambi kokuba uhlaziyo lwe-DC luqwalasele ukutshintshwa kwe-inverter, phendula:

Imeko ye-inverterImisebenzi yoyilo lwezakhiwo
Onempilo + oxhaswayoLondoloza kuqala; vavanya i-AC.
Ixabiso elibalulekileyo lewarantiEndaweni yoko kufuneka isigqubuthelo esomeleleyo.
Isiphelo sobomi / asisetyenziswaThelekisa i-AC ne-DC kwakhona.
Ukuthengwa kwesinye sele kuxhaswe ngemali.Musa ukufaka zonke iindleko zokutshintsha kwi-DC.
Kucwangciselwe ukutshintshwa okukhulu kwamandla.I-DC iyakholeleka ngakumbi
I-inverter ekhoyo ayikwazi ukumelana nomthwalo wexesha elizayo.Uyilo olutsha lunokungaphepheki.

Iingxoxo zangoku zase-Australia ngeeprojekthi ze-hybrid nazo ziye zichonga ukwaluphala kwee-inverter kunye nezivumelwano zokudibanisa esele zikho njengezithintelo eziphambili zokuphucula izixhobo ezikhoyo. Iindaba Zogcino-Amandla

Ukudityaniswa kwe-AC kunokugcina isixhobo selanga esisebenzayo.

Eyona ngenelo iphambili yokudibanisa nge-AC kukuba Ugcino lomda.

Londoloza apho kunokwenzeka khonaYongeza okanye uqinisekise kwakhona
Iimodyuli ze-PV kunye neentsimbiIkhabhathi kaBess
I-inverter ye-PV esele ikhonaIbhetri PCS
Ucwangciso lwe-PV MPPTI-AC feeder kunye nebrekeri
Iindlela zamakhebula e-PV DCUmthamo weswitshibhodi
Ujongano lwe-PV olukhoyoI-PCC mita / ii-CTs
Iinkqubo zolondolozo kwicala le-PVEMS / umlawuli wesityalo
Umda wewaranti ye-PV ekhoyoUlungelelwaniso lokhuselo

Oku kukwanciphisa ukusasazeka koxanduva phakathi kwe-EPC yelanga yokuqala kunye nomda omtsha we-BESS.

Efama yelanga yaseMokoan e-Australia, i I-80 MWh BESS idityaniswa nge-AC kwifama yelanga esebenzayo eyi-58 MW., ukwabelana ngonxibelelwano lwegridi nokusebenza kunye njengobutyebi obunye. Uhlaziyo loQoqosho

Musa ukuvula kwakhona iphakheji ye-PV esebenzayo ngaphandle kokuba ixabiso elongezelelweyo liyifuna.

Ukudityaniswa kwe-DC kuya kusomelela xa isakhiwo se-PV sele sitshintsha.

Ukudityaniswa kwe-DC kuya kufumana inkxaso xa iprojekthi sele itshintsha okanye iyila ngokutsha inkqubo ye-PV.

Izinto eziqhelekileyo ezivusa iimpawu ziquka:

Ixabiso elinokubakhoOkufuneka kungqinwe
Uguqulo oluphindaphindwe kancinci / BoSYeyiphi imixholo eshwabana ngokwenene?
Ukuchacha kokusikaZingaphi ii-kWh ezinokufunyanwa?
Uyilo oludityanisiweyo lwenkqubo yokudibanisaIngaba inkqubo ye-grid iyiphatha ngokwahlukileyo ngokwenene?

Thelekisa Ukufakwa kwesona simo samandla + i-AC BESS kunye Ukufakwa ngokutsha kwamandla okucwangcisiweyo + i-DC BESS, hayi inkqubo entsha ye-DC echasa i-inverter ekhoyo engabikhoyo nexabiso elinguziro.

Imithetho yoqhagamshelo kugridi inokwenza ukudityaniswa kwe-DC kube yiprojekthi ekhawulezayo.

E-Australia, iingxoxo zeshishini zango-2026 ziye zanika ingxelo yokuba ezinye iiprojekthi ze-hybrid ezidityaniswe nge-DC zinokunciphisa i-Generator Performance Standard okanye inkqubo yokuqhagamshela nge ukuya kutsho kwiinyanga ezintandathu kuba i-PV ne-BESS zivavanywe njengokuphela kwenkqubo edibeneyo. Le ngxoxo inye ilumkisile ukuba itekhnoloji ye-inverter endala kwiiprojekthi zokuhlaziya ingaphinda ivule umsebenzi wokudibanisa. Iindaba Zogcino-Amandla

Loo nani weenyanga ezintandathu Asiyondlela yokucinga efanayo kuye wonke umntu.

Jonga:

Ixesha loqhagamshelwano kunye nomngcipheko wemvume zifanele ukuba kwimodeli yeendleko zolwakhiwo.

Thelekisa ukusebenza kakuhle kwindawo enye yendlela, umda kunye nendawo yokusebenza

Uthelekiso lokusebenza luyasebenza kuphela xa iinkalo ezintathu zifana:

IndlelaUkufaneleka kwezakhiwo
PV → UmthwaloUguqulo lwebhetri lusenokungathathi nxaxheba
I-PV → Ibhetri → UmthwaloI-DC ingazisusa izigaba zoguqulo.
Igridi → Ibhetri → UmthwaloInzuzo kwicala le-PV isenokunyamalala
I-PV enesikro → Ibhetri → UmthwaloIxabiso lisenokuthi livele ekufunyanweni kwamandla angenakufikeleleka.

Xa uphonononga ibango lokonga, buza:

Kwi-MegSolid Energon 261, eyapapashwayo 90% Umfanekiso bubalaseleyo bokusebenza kwenkqubo, hayi i-RTE echaziweyo.

Linganisa i-PV Clipping Phambi Kokuyinika iXabiso leedola

ILR = i-PV DC nameplate / i-inverter AC rating

Umzekelo:

600 kWp PV ÷ 500 kW i-inverter = 1.20

Kwenza njalo hayi Oku kuthetha ukuba i-100 kW isoloko ilahleka.

Use:

Emva koko bala:

Amandla alinganisiweyo agciniweyo

Amandla akhoyo ngelixa i-BESS inendawo yokongeza i-charge.

Amandla anokufunyanwa ngolwakhiwo olucetywayo

Kwimeko yeshishini kufanele kubekho kuphela isixa sokugqibela.

Ukucutha Akufani nokuncitshiswa kokuthunyelwa ngaphandle

ImekoIsizathuImisebenzi yoyilo lwezakhiwo
Ukucutshungulwa kwe-inverterUmda wokuguqulwaUgcino lwe-DC lunokufikelela kumandla awayenokuphela.
Ukuncitshiswa kokuthunyelwa kwamanye amazweIsenzo solawulo se-PCCUgcino lwe-AC okanye lwe-DC lunokunceda.
Ukuncitshiswa kwamandla okushushuIqondo lobushushuI-Topology ayilungisi unobangela oyintloko.
Umda wokuthunyelwa kwegridiUmyalelo wangaphandleKuxhomekeke kumalungelo okusebenza

Musa ukufaka wonke amandla akho agodliweyo kwishredispati enophawu oluthi “clipping recovery.”

Imida Yokuthumela Ngaphandle Inokutshintsha Isigqibo Sezakhiwo

Umzekelo:

Ixabiso lokusebenzaAmandla
I-PV500 kW
LayishaI-100 kW
Umda wokuthumela ngaphandle300 kW

500 − 100 = 400 kW amandla okuthumela kumazwe angaphandle

Umlawuli kufuneka asuse I-100 kW.

Uluhlu olusebenzisekayo:

Uyilo olukhethiweyo kufuneka luxhase Usukelo olunye lwamandla ombane kwi-PCC.

I-MegSolid ESSA0100B-0215 ifaka i-100 kW ukuze igcine umda wokuthumela ngaphandle we-300 kW kwi-PCC.

Ukudityaniswa nge-AC akuthethi ukuba zizinto ezahlukileyo ngokwasemsebenzini

Iprojekthi yaseQuorn Park idibanisa Amandla elanga angama-98 MW anesistim ye-BESS edibene ne-AC enama-20 MW / 40 MWh phantsi kweMigangatho yokuSebenza kweZijeneretha enye edityanisiweyo kunye nomlawuli omnye wesikhululo sombane. Iindaba ze-ESS

IsalekoUxanduva
BMSImida yebhetri
PCSUkuphunyezwa kwamandla ebhetri
I-inverter ye-PVIsiphumo se-PV
EMS / PPCUjoliso lwezityalo olulungelelanisiweyo
Imitha ye-PCCUmlinganiselo wemida wokwenene

Ukuqhagamshelwa ngombane ≠ ukudityaniswa kolawulo ≠ ubhaliso kwinethiwekhi.

Ii-inverters ekwabelwana ngazo nezahlukileyo zenza imida yamandla eyahlukileyo.

I-PV ekhoyo = 450 kW
Isicelo sebhetri = 150 kW
I-inverter ekwabelwana ngayo = 500 kW

Imithombo zizonke ziyi-600 kW, kodwa yi-500 kW kuphela enokudlula kwi-converter ekwabelwana ngayo.

I-AC coupling yahlula imida yomguquli, kodwa umphumo odityanisiweyo usenokuthintelwa:

Ibhodi yezwekazi → Itransfoma → PCC → Isivumelwano sokuthumela ngaphandle

Soloko wahlula:

Iswitshibhodi neTransformer esele ikhona zinokwala uhlaziyo lwe-AC.

JongaUkungaphumeleli okunokwenzeka
Isibonda sombaneAmandla ombane anganelanga
Umsiki / umondliAkukho ndlela yokudibanisa esebenzayo
IguquleliUmthwalo wecala ugqitha umlinganiselo
IntamboI-Ampacity iyasilela
UkhuseloUlungelelwaniso luyasilela
UkupimaUmda we-PCC awugqitywanga
Iinkonzo zonyango ezingxamisekileyoAkunakunyanzeliswa umgama wokwenene ongaphezulu.

Isikrini sokutshutshiswa kwangaphambili:

Umrhumo wegridi we-BESS ovumelekileyo
Ubuncinane obuvumelekileyo kwintloko yokungenisa/yogcino-lwelo
− Umthwalo oqhubekayo
− umda

I-PCS eyi-250 kW ayivelisi i-250 kW yamandla okuhlawulisa avumelekileyo xa kusele i-80 kW kuphela yomthamo oseleyo wenethiwekhi.

Amandla Okuhlalutya Ngumgqibo Woyilo Owahlukileyo

Ibhetri ifakiwe ≠ i-backup iyafumaneka.

Kusafuneka ukugcina okusemva:

Ukudityaniswa kwe-AC/DC kuphendula kuphela apho i-PV nebhetri zidibana khona.

Thelekisa ii-Failure Domains kunye ne-Serviceability

Izixhobo azifumanekiUlwakhiwo lwe-AC olwahlulweyoUlwakhiwo lwe-DC olwabelwana ngalo
I-inverter ye-PVUBESS angahlalaKuxhomekeke kwi-converter ekwabelwana ngayo.
BESS PCSI-PV ngesiqhelo ihlalaKuxhomekeke kudityaniso
Ibhetri/Ulawulo lweBhetriI-PV ingahlalaUlawulo oluxubeneyo lufuna ukuphononongwa.
Impazamo ye-PV DCIbhetri isenokuba yodwaUmda oqhelekileyo we-DC ufuna ukufundwa
EMS/PPCKufuneka ukhuseleko olungagungqiyoKufuneka ukhuseleko olungagungqiyo
Imitha ye-PCCKufuneka ukulawula ukubuyela emvaKufuneka ukulawula ukubuyela emva

Buza:

Ukuba esi sithako sihlukaniswe iiyure ezine, zeziphi iinkonzo zesiza eziseleyo?

Ukwandisa Kuthetha Izinto Ezithathu Ezahlukileyo

UkwandisaImpembelelo engundoqo
Ngaphezulu kwee-PV kWUveliso lwelanga / i-inverter / ukunqamla
I-kilowathi ezingaphezulu zebhetriAmandla okutshaja nokukhupha
I-kWh yebhetri eninziUbude bexesha

Chaza izigaba zexesha elizayo njengoko:

Isiqendu → PV kW → BESS kW → BESS kWh → Imfuneko ye-PCC

—hayi nje “okwandekayo.”

Ukudityaniswa kwe-AC akukhawulelwanga kwiinkqubo ezincinci zolungiso olutsha.

Iimveliso zorhwebo zangoku zibonisa ukuba ukudityaniswa kwe-AC kuyilwe kwezixhobo zokugcina ezine-three-phase C&I kunye nezo zokugcina ezimodular zomgangatho we-MWh. Umzekelo, iqonga le-Enphase i-2026 C80, lixhunywe nge-AC kwaye lichazwa njengelokwandisa isiseko ukusuka kwi-80 kWh ukuya kwi-2 MWh, ngelixa lixhasa ii-inverter ze-PV zorhwebo ezivela kwezinye iinkampani. Inxalenye

Ubungakanani beprojekthi bodwa abukhethi itopoloji.

Musa ukudlulisa iipesenti zeendleko zesikali senkonzo kwi-C&I Retrofit

Thelekisa umda wokwenene:

Into yexabisoUmoya opholileyoDC
I-inverter ye-PV esele ikhonaNgokuqhelekileyo igcinwaInokutshintsha
Iintambo / MPPTNgokuqhelekileyo igcinwaInokutshintsha
Iguquleli yebhetriUhlukanisa i-PCSEkwabelwana ngayo/edityanisiweyo
Umgca wokondla we-ACKudla ngokongezwaKuxhomekeke
Ukhuselo lwe-DCUtshintsho olulinganiselweyoInokwandiswa
Ukuphinda uqaliseNgokuqhelekileyo kunomsebenzi omncinci kwicala le-PV.Inokunyusa
Impembelelo yokuvunywaOchaphazela indawo ethileOchaphazela indawo ethile

Use:

Iindleko zofakelo ezinyukayo
÷
Ixabiso elonyukayo lobomi bonke

—hayi ipesenti eqhelekileyo evela kwenye iklasi yeprojekthi.

Thelekisa Umda Wokuhlaziywa Okupheleleyo neXesha Lokumisa Umsebenzi

Ingoma

Impembelelo iyonke yokulungiswa kwakhona = CAPEX + ubunjineli + iindleko zokuvala + ilahleko yexabiso le-PV + ukuqaliswa ngokutsha

Apho iMegSolid ilingana khona noyilo lwezakhiwo

Imfuneko yeprojekthiIndlela yokuqalaUmda
Umthamo wekhabhathi ongange-100 kWESSA0100B-0215100 kW / 215.04 kWh
Amandla angakumbi akwikhabhathi / ukupholisa okungukwi-liquidI-Energon 261261.24 kWh / 125 kVA
Ulwakhiwo olwahlukileyo lwe-PCSI-MEGA TS30–500 kW

Amaxabiso alawulwayo e-ESSA0100B-0215 aquka i-100 kW, i-215.04 kWh, i-768 V, i-0.5C kwi-25°C kunye nokupholisa komoya okukrelekrele. Iinketho zocwangciso lwe-PV ziboniswa njenge-120 / 180 / 240 kW.

I-Energon 261 isebenzisa i-LFP eyi-314 Ah kunye nokupholisa okungamanzi. Gcina 125 kVA njengamandla abonakalayo 90% njengekwanakho eliphezulu lenkqubo.

Iireyithingi zePCS ezilawulwa yiMEGA TS ziqala ukusuka 30 ukuya kwi-500 kW.

I-Matrix Yezigqibo yeLanga yorhwebo: Ekuqhagamshelweni nge-AC xa kuthelekiswa noku-kuqhagamshelweni nge-DC

ImekoUmoya opholileyoDCUbungqina obuyintloko
I-inverter esempilweni esele ikhonaOomeleleyoEzantsiIxabiso eliseleyo le-asethi
Ukutshintshwa kucwangcisiweOomeleleyoOomeleleyoIindleko ezongezelelweyo
Uhlengahlengiso oluncinci lwe-PVOomeleleyoEzantsiUmda wokulungiswa kwakhona
Ukuchetywa kwezintoElinganiselweyoOomeleleyoIi-kWh ezinokufunyanwa
Ukucheba incophoOomeleleyoKungenzekaUkuthunyelwa okuzimeleyo
Uqhagamshelwano lwe-AC luyathintelwaIsifundoAmandla angaphakathiUjongano lokugqibela
I-PV+BESS entshaOomeleleyoOomeleleyoUkuthunyelwa / Isiphelo / iGridi
Ugcino-mbuyiseloUphononongo olwahlukileyoUphononongo olwahlukileyoUbunjineli beziqithi

Izinto Ezintandathu Ezifunekayo Phambi Kokukhutshwa Koyilo Lwesakhiwo

Ngaphandle kwezi ngeniso, itopoloji isengumbono nje.

Umgaqo-siseko Wokugqibela

Umthi wesigqibo wokukhetha ukugcinwa kwebhetri okudityaniswe nge-AC okanye nge-DC, ngokusekelwe kwimeko ye-inverter, iziseko ezingundoqo, kunye nobungqina bokunqunyulwa.

Ulwakhiwo olukhethwayo loluya oluhambisa ukuthunyelwa okufunekayo kwi-PCC nge- utshintsho lwezixhobo olungenasizathu kunye netyala loshishino elomeleleyo kubo bonke ubomi balo.

Imibuzo Ebuzwa Rhoqo

Ukudityaniswa kwe-AC kudla ngokuba yeyona skrin yokuqala yokulungiswa kwakhona xa i-inverter ye-PV esele ikhona isenobomi obuncedo obuseleyo kwaye inkqubo ye-AC ingakwazi ukwamkela enye i-PCS. Oku kugcina inxalenye enkulu yepropathi ye-PV efakiweyo, kodwa i-switchboard, i-transformer, i-PCC kunye nezilawuli kusafuneka zikwazi ukudlula.

Ukudityaniswa kwe-DC kuya phezulu xa sele kucwangcisiwe ukutshintshwa kwe-inverter okanye ukuphinda kufakwe amandla e-PV, ukunqunyulwa okulinganisiweyo kunexabiso elinokubuyiswa, okanye inkqubo yengingqi yokudibanisa ikhuthaza isikhululo esidibeneyo selanga kunye nogcino-bhetri.

Hayi. Thelekisa indlela yamandla efanayo, umda wokulinganisa kunye nendawo yokusebenza. Ukuqhagamshela nge-DC kunokususela amanqanaba aguqulo okutshaja i-PV kwi-battery, kodwa elo ncedo lisenokungabaluleki kangako kwiprojekthi elawulwa kukutshaja kwi-grid okanye ukunciphisa umthamo ophezulu.

Iyakwazi ukufunxa amandla agqithisileyo afikelela kwi-AC bus, kodwa ayikwazi ukuzihlaziya ngokuzenzekelayo amandla e-DC angenakuguqulwa yi-inverter ye-PV esele ikhona emva kokuba ifikelele kumda wayo ophezulu we-AC.

Sebenzisa isiphumo se-AC se-inverter esinamachaphaza exesha kunye nedatha ye-DC/MPPT ekhoyo, ukukhanya kwelanga kunye nemeko yokusebenza. Ireyithingi ye-AC ye-inverter ikhutshwa kwireyithingi ye-PV DC nameplate ayiyondudumo yonyaka enqunyulweyo.

Hayi. I-clipping ivela kumda wuguqulo. Ukuncitshiswa kokuthunyelwa ngaphandle linyathelo lolawulo elijolisiweyo kwi-PCC okanye komnye umda wegridi.

Ewe. Umlawuli wesiza se-EMS okanye wesikhululo sombane angalungelelanisa ii-converter ezahlukeneyo ze-PV neze-BESS ukuya kuthi ga kwipali enye yokulungelelanisa umbane (PCC).

Hayi. I-voltage yebhetri, i-voltage ye-PV, i-current, i-MPPT, uguqulo lwe-DC/DC, ukhuseleko kunye namandla okulawula i-inverter konke kufuneka kuqinisekiswe.

Hayi. Ibekap ufunisa umda we-island, ukwahlulwa kweenkonzo, amandla okwenza igridi apho kufuneka khona, imithwalo ekhuselweyo, ukhuselo kunye nolandelelwano olucacisiweyo lokubuyisela.

Hayi. Iiprojekthi zaseGreenfield zinokukhipha izixhobo eziphindaphindiweyo, ngelixa iisiza zaseBrownfield zinokuba sele zinazo ii-inverters ze-PV ezixabisekileyo kunye neziseko ezingundoqo ze-DC. Thelekisa umda wokwenene wongezelelo ofakelweyo.

Isebenzisa iindlela ezahlukeneyo zoguqulo lwe-PV nebhetri ezidityaniswe kwicala le-AC. Kuhlaziyo, i-inverter ye-PV esele ikhona isoloko ishiyeka ngelixa i-BESS isebenzisa eyayo i-PCS ehamba macala omabini.

I-PV nebhetri zilungelelaniswa kwicala le-DC phambi kwinqanaba eliphambili lokuguqulwa kwe-AC, kusetyenziswa rhoqo amanqanaba e-DC/DC kunye nesakhiwo se-inverter esabelwana ngaso okanye esidibeneyo.

Qokelela imodeli nobudala be-inverter ye-PV, amanqanaba e-DC ye-PV kunye ne-AC ye-inverter, ubungqina bokunqunyulwa, idatha edityanisiweyo ye-PV/umthwalo, imida ye-PCC kunye neye-transformer, umthwalo womsebenzi webhetri kunye neemfuno zokudibanisa zalapha.

IMegSolid (Hong Kong) Limited igxile kuphando nophuhliso, uyilo kunye nokubonelela ngeenkqubo zokugcina amandla ezikumgangatho ophezulu. Ngalo mava obuchwepheshe esinawo emva kweminyaka elishumi, sinikezela nge-ESS yekhabhathi yangaphandle eyenziwe ngokweemfuno zomthengi, ii-inverters zasekhaya kunye nezisombululo zamandla eziphathwayo kubathengi behlabathi jikelele.
WhatsApp/Wechat: +852 59811073

Fumana isisombululo sakho seMegSolid sokugcina amandla kwiiyure ezingama-24.

Ngqo kumvelisi weebhetri ze-solid-state. Fumana isiphakamiso se-ESS esenziwe ngokweemfuno zakho, uhlalutyo lwe-ROI, kunye nesindululo senkqubo kwiqela lethu lobunjineli.

Into Oza Kuyifumana

Ityelelwe ehlabathini lonke:

UL, IEC, UN38.3, China Classification Society, GB36276-2023, RoHS

Iimodeli ezishushu:

Izicelo:

Iifektri · Iifama zelanga · Ezemigodi · IiZiqithi · Iziko leDatha