400
Rated voltage (V)
98.7%
Max.efficiency
±1%
Voltage accuracy
THDi
<2%
THDV
3% (linear load)
Charge/discharge switching time (ms)
<20
Relative humidity
DC(battery)
Our Core Values
DC(battery)
Model
PMA080 | PMA0105 | PMA0125
Max. DC power (kW)
96 | 126 | 150
DC voltage range (V)
615~950Vdc(3W+PE)/650~950Vdc(3W+N+PE)
DC full load voltage range (V)
650-950Vdc(3W+PE)/680-950Vdc(3W+N+PE)+230
Max. DC current (A)
±150 | ±195 | ±230
Voltage stabilization accuracy
±1%
Current stabilization accuracy
±2%
AC(on-grid)
Rated AC power (kW)
80 | 105 | 125
Max. AC power (kWA)
3W+PE or 3W+N+PE
Voltage scale
3W+PE or 3W+N+PE
Rated voltage (V)
400
Rated AC current (A)
115 | 150 | 180
Max. AC current (A)
138 | 180 | 216
Allowable grid voltage range (V)
400Vac±15%
Allowable grid frequency range (Hz)
50±2Hz/60±2Hz
Power factor adjustment range
-1 ~ +1
AC( off-grid)
Rated AC power (kW)
80 | 105 | 125
Max. output current (A)
138 | 180 | 216
Max. AC power (kWA)
96 | 126 | 150
Rated voltage (V)
230/400
Rated frequency (Hz)
50Hz/60Hz
Voltage accuracy
±1%
Frequency accuracy
(50Hz/60Hz ±0.1%)Hz
THDV
3% (linear load)
Unbalanced load capacity
Supports 100% single-phase unbalance
Overload capacity
≤110%,continuous ;≤120%,2min ;>120%,200ms
System
Max. efficiency
98.7%
Charge/discharge switching time (ms)
<20
Ingress protection
IP20 (power compartment) IP6X (control compartment)
Relative humidity
<95%(non-condensing)
Operating temperature range (℃)
-30~+60 (>45 derating)
Max. operating altitude (m)
5000(>3000 derating)
Communication interface
RS485/CAN/Ethernet
BMS/EMS access
Support
Dimension W*D*H (mm)
483*680*174 19inch 4U 483*680*220 19inch 5U | 483*680*174 19inch 4U 483*680*220 19inch 5U | 483*680*174 19inch 4U 483*680*220 19inch 5U
Weight (kg)
48(back wiring) 50(front wiring) | 48(back wiring) 50(front wiring) | 48(back wiring) 50(front wiring)
