Iindawo zokwenza iwayini zaseSpain ezijongene nesikhewu sokungenisa esiyi-75 kW kunye nerhafu yokukhupha i-AC yemihla ngemihla eyi-136.25 kWh kufuneka zisebenzise i MegSolid ESSA0100B-0215 kwisimo somsebenzi esichaziweyo sokuvuna-nesolara. Amandla ayo aqikelelweyo e-AC angama-100 kW kunye namandla agciniweyo aqikelelweyo angama-215.04 kWh zombini ziyawagqitha imida yalo msebenzi, ngelixa ikhabhathi engama-50 kW / 100.352 kWh yona ingakwenziyo oko.
Ibhetri kufuneka igqume umsantsa wokungenisa olulinganisiweyo kunye nexesha elipheleleyo lokusebenza; i-PV-array kWp ayimiseli isilinganiselo se-BESS. I-ESSA0100B-0215 idibanisa loo mandla namandla-gcino kunye ne-EMS edityanisiweyo, i-transformer yokwahlula eyakhelweyo kunye nojongano lwe-400 V. Ulawulo lokunciphisa iincopho ze-PCC kwaye Ukulungiswa kwakhona kwenkqubo yamandla elanga edityaniswe ne-AC Emva koko qhagamshela ikhabhathi kwisixokelelwano esele sikho somthombo wewayini.
ESSA0100B-0215 Iquka umthwalo weWinery we-75 kW / 136.25 kWh
Ukucubungula imfuno kufikelela 245 kW ngokuchasene no 170 kW kungenisa i-target, ukudala i- 75 kW Imfuneko yebhetri:
Amandla e-BESS afunekayo = 245 kW ukungeniswa kwesiza − 170 kW ukungeniswa okujonjiweyo = 75 kW
ESSA0100B-0215 izibonelelo Amandla e-AC alinganisiweyo angama-100 kW, ukushiya Umthamo wamandla ongezelelweyo ongama-25 kW Ngaphezulu kwesikhewu esilinganisiweyo phambi kokuncitshiswa kwesiza nemida yokusebenza. Yayo Amandla ebhetri aqikelelwe kwi-215.04 kWh ikwabonelela iprojekthi ngeklasi yamandla eyaneleyo ukuvavanya umsebenzi opheleleyo wokuqokelela nokusebenza ngokuhlwa.
Ikhabhathi ye-ESSA ibeka ibhetri, isigaba sokuguqula amandla, i-transformer yokwahlula eyakhelweyo kunye nemisebenzi ye-EMS kwiqonga elinye langaphandle. Umthengi ufumana echaziweyo 400 V, Ikhulu namashumi amane anesine A, Ipasi-5, i-4 umda womveliso kunye nonxibelelwano lwe-RS485 ne-TCP-IP, kunokuba kwahlulwe imisebenzi esisiseko yokugcina ngaphandle komgaqo-nkqubo omnye wekhabhathi.
| Imfuneko yokuthenga | Umrhumo wewayini | ESSA0100B-0215 isiphumo |
|---|---|---|
| Ukuncitshiswa kwexesha eliphezulu lokungenisa | 75 kW | Amandla e-AC aqikelelwe kwi-100 kW; umda oqikelelwe kwi-25 kW |
| Vuna amandla aphezulu | 75 kW kwimizuzu engama-45 = 56.25 kWh AC | Kubandakanyiwe kuvavanyo lwamandla |
| Imveliso yangokuhlwa | I-80 kWh AC | Umrhumo odityanisiweyo ufikelela kwi-136.25 kWh AC. |
| Amandla ebhetri alinganisiweyo | Kufuneka ngaphezulu kwe-136.25 kWh ye-AC phambi kokulahleka kunye negcina le-SOC. | Iklasi yamandla enqanaba le-215.04 kWh |
Ikhabhinethi ye-50 kW ayikwazi ukwenza umsebenzi oyimfuneko.
I-ESSA0050B-0100 yimveliso yeMegSolid esebenzayo kwiindawo ezincinci zokwenza iwayini, kodwa apha incinci kakhulu ngenxa yezizathu ezibini ezizimeleyo.
Yayo Amandla e-AC aqikelelwe kwi-50 kW ayikwazi ukuhambisa i 75 kW Ukuncipha. Nokuba kumveliso epheleleyo, ukungeniswa kwegridi kuhlala ku 195 kW, okuyo Ngaphezulu kwe-25 kW Usukelo lwe-170 kW:
Ukungeniswa kwesiza se-245 kW − isiphumo se-BESS se-50 kW = ukungeniswa okuseleyo se-195 kW
Yayo Amandla ebhetri aqikelelwe kwi-100.352 kWh ikwayo 35.898 kWh ngaphantsi okufunekayo 136.25 kWh AC ulandelelwano phambi kokuba kubalwe ilahleko yoguqulo, ukusetyenziswa kwezixhobo zokuncedisa okanye isipaji sokusebenza se-SOC. Akukho sethingi ye-EMS enokulungisa ukunqongophala kwangempela kwamandla e-PCS okanye amandla agciniweyo.
I- Iklasi yekhabhathi ye-50 kW / 100 kWh kusahlala yeyona ndlela ifanelekileyo yeMegSolid xa isikhewu esilinganisiweyo sihlala siphakathi kwe-50 kW kwaye amandla e-AC asetyenziswayo aqinisekisiweyo anokwanela isiganeko sonke. Kwi 75 kW ne-136.25 kWh AC, ESSA0100B-0215 iyalingana ngqo nomsebenzi ochaziweyo.
I-Full Discharge Window ingqina inzuzo ye-215.04 kWh
Ukunqongophala kwamandla e-75 kW kwindawo yokwenza iwayini kuthatha amaxesha amathathu angemizuzu eli-15 ngalinye. Elo xesha lokunciphisa umthamo ophezulu lufuna 56.25 kWh AC. Ngokuhlwa ukupompa, ukupholisa nokuqhuba inkqubo kuye kufuneke enye I-80 kWh AC, ukuzisa ulandelelwano olulinganisiweyo kwi 136.25 kWh AC.
Incopho yokuvuna: 75 kW × 0.75 h = 56.25 kWh AC
Umsebenzi wangokuhlwa: 80 kWh AC
Umrhumo wonke wokukhupha: 56.25 + 80 = 136.25 kWh AC
Gcina iNominal Energy yahlukileyo kwiVerified AC Delivery.
ESSA0100B-0215 ine 114.688 kWh yamandla ebhetri angaphezulu alinganisiweyo kune-ESSA0050B-0100. Xa ithelekiswa nomthwalo we-AC we-136.25 kWh, isilinganiso sayo se-215.04 kWh sidala 78.79 kWh umlinganiselo wamandla oqhelekileyo kweelahleko zoguqulo, umgangatho we-SOC ovunyelweneyo kunye nomda wenzuzo yokusebenza. Umahluko we-78.79 kWh ayiyondleko ye-AC enokuhanjiswa ngokuzenzekelayo; ukuqaliswa komsebenzi kufuneka kuqinisekise umphumo we-AC onokusetyenziswa kumagreni avunyelweneyo amandla, iqondo lobushushu kunye nemida ye-SOC.
I-ESSA0100B-0215 ingamiselwa ngokuchasene noluhlu olunye olupheleleyo lwemveliso; i-ESSA0050B-0100 iyasilela kuzo zombini iiskrini zamandla kunye ne-energy phambi kovavanyo lwaselayithi. Oku kuphepha ukuthenga ikhabhathi enciphisa i-peak ngaphandle kokufikelela kwinjongo kwaye ize iphelelwe ngaphambi kokuba kuphele imveliso yangokuhlwa.
Sebenzisa iKhabhathi efanayo ye-ESSA100 kwiHarvest Peaks kunye neSolar Shifting.
Imfuno yovuno kunye nokugqithiseka kwamandla elanga angavunwanga zidala imisebenzi eyahlukileyo kwikhabhathi enye. Ngethuba lokulungiswa kweediliya, ukunciphisa umthamo ophezulu kukhusela usukelo lokungenisa. Ngaphandle kovuno, ibhetri igcina ukugqithiseka kwamandla e-PV asemini anokusetyenziswa ize ikhulule la mandla ngexesha lemfuno yasemva kwexesha kwindawo yokwenza iwayini.
Igama le-PV kuphela alimiseli ubungakanani bebhetri. Amandla okutshaja afanelekileyo ngumhlumelo oseleyo isigaba ngesigaba emva komthwalo we-winery:
Intsalela ye-PV efumanekayo = Isixa esiphezulu (Isiphumo se-PV − Umthwalo wendawo ehambelanayo, 0) × Ixesha lesigaba
Bala ukutshaja kwelanga ngokusuka kwisalathu esilinganisiweyo.
Kumveliso ye-PV eyi-78 kW kunye nomthwalo wendawo oyi-33 kW, 45 kW iyafumaneka kumda we-AC. Izikhewu ezibini zemizuzu engama-30 zibonelela 45 kWh AC phambi kuguqulelo kunye nemiqathango yokusebenza. I- Ukuphambili kokutshaja i-PV Kufuneka kugcinwe indawo ye-SOC phambi kokuba kufike loo mdiza; ukuzalisa ibhetri isuka kwinethiwekhi kwangoko kakhulu kungavala ukufunxa amandla elanga.
Imisebenzi edityanisiweyo ye-EMS yeMegSolid, uqikelelo lwamandla ebhetri kunye noqikelelo lwexesha lokukhupha umbane zinika i-EPC iqonga lemveliso kuzo zombini ezi zibophelelo. Ufikelelo olulodwa kwimithwalo, ibhetri, igridi, ijeneretha yedizili kunye ne-PV lukwaxhasa uyilo olubanzi lwamandla kwindawo yokwenza iwayini. Ngaphandle kwesivuno, amandla e-PV afumanekayo emini anokugcinwa ukuze asetyenziswe kamva kwimfuno yendawo yokwenza iwayini.
Iprojekthi yaseSpeyin yomzi-mveliso wewayini ibonisa ipateni efanayo yokunciphisa incopho.
Iprojekthi yeCEGASA iBodega Vega Tolosa eAlbacete, epapashiweyo, idibanisa 100 kWp yamandla elanga, 187.6 kWh yokugcinwa kwamandla, ukunciphisa incopho kunye nokutofwa kwe-zero. Iingxelo zokurekhoda iiprojekthi I-€19,800 ngonyaka ekunciphiseni iindleko zamandla kwaye Iitoni ezili-10.2 zokonga i-CO₂ yofakelo olunjalo. Bona i Irekhodi leprojekthi yaseBodega Vega Tolosa.
Amaxwebhu eprojekthi apapashiweyo achaza ugcino, ukuzisebenzisa, ulawulo lwencopho kunye nolawulo lokuthumela ngaphandle kwindawo enye yokwenza iwayini eSpain. Awaseki isilinganiso kwelinye ixesha. Inzuzo yeMegSolid kukuba uluhlu lwe-ESSA luguqula umthwalo olinganisiweyo wendawo entsha yokwenza iwayini lube sisigqibo esithe ngqo sekhabhathi: 50 kW / 100.352 kWh lomda omncinci okanye 100 kW / 215.04 kWh kumthwalo we-AC we-75 kW ne-136.25 kWh ovavanywe apha.
Gcina iimali ezigciniweyo zeProjekthi epapashiweyo zahlukile kwiWinery entsha.
Naluphi na uqikelelo lwezorhwebo lusekelwe kwitarifu yombhiyo wewayini, iindleko zokungenisa eziphetshweyo, ixabiso lokuthumela kumazwe angaphandle, indlela yokuhlawula ixabiso eliphezulu kunye neshedyuli yokusebenza. Isindululo semveliso asisekelwanga ekukopisheni ukonga kweprojekthi enye; sikwimeko yokuba i-ESSA100 icacise imida yobuchwepheshe emibini elinganisiweyo.
I-Zero Export, i-EMS Priority kunye ne-Meter Direction Kufuneka Zisebenze NjengeNkqubo Enye
yaseSpeyin UMmiselo Wokwenene 244/2019 ichaza i-*autoconsumo sin excedentes* njengokusetyenziswa ngokwakho okunendlela ethintela amandla agqithisileyo ukuba angafikeleli kwinethiwekhi. I-ITC-BT-40 elungisiweyo phantsi kwe Umgaqo-nkqubo weTekhnoloji ye-Electro yomtsindo ophantsi ifuna ukuba inkqubo engathumelwa kumazwe angaphandle ihlangabezane neemfuno ezifanelekileyo zolawulo novavanyo. La migaqo iguqula uvavanyo lokwamkelwa kwendawo, hayi ipleyiti yegama ye-ESSA.
Misa ukuthunyelwa kwangaphandle kwe-Zero ngaphezulu kokuhanjiswa kwezoqoqosho
Sebenzisa olu luhlu lwezinto eziphambili zokulawula:
- Gcina umda wokuthunyelwa kwangaphandle onyanzelekileyo kwindawo yokudibanisa.
- Khusela usukelo lokungenisa lwefama yewayini ngexesha lokuvuna okukhulu.
- Khuphela umbane oseleyo welanga ngelixa uhlonipha i-SOC nemida yamandla.
- Gcina amandla aneleyo kwisiganeko esilandelayo somdlalo esicwangcisiweyo.
I-MegSolid ibonelela ngemisebenzi edityanisiweyo ye-EMS kunye nendlela yonxibelelwano ye-RS485/TCP-IP ngaphakathi kwemida yemveliso. I-PCC meter yangaphandle, isilawuli sendawo, i-PV inverter esele ikhona kunye nesicwangciso sokukhusela zisadinga ukumiswa ngokunxulumeneyo. Umda wolawulo lokungathunyelwa kwamanye amazwe kufuneka ilinganiswe kwindawo efanelekileyo, kwaye i Uvavanyo lwe-polarity ye-CT Kufuneka kungqineke ukuba ukungeniswa nokuthunyelwa ngaphandle kutolikwa ngendlela echanekileyo.
I- Uluhlu lwezinto eziphambili kwi-EMS Ithintela umyalelo wokurhweba nge-intanethi ukuba ungagqithi kumda wokuthumela impahla ngaphandle ovunyiweyo okanye udale ixesha elitsha eliphezulu lokungenisa impahla.
Chaza umda wofakelo lombane nolwezakhiwo lwe-400 V.
Jonga isikhundla se-400 V Feeder kunye nezixhobo
ESSA0100B-0215 ibonelela nge Ujongano lwe-AC olulinganiselwe kwi-400 V, 144 umbane we-AC onomlinganiselo we-A, ukupholisa umoya okubalulekileyo kunye ne- Ipasi-5, i-4 Isingxobo. Imilinganiselo yaso epapashiweyo yile 2,450 × 1,550 × 2,400 mm, kwaye ubunzima bayo yi Ii-kilogram ezingama-3,900. Iinqobo ezipapashiweyo zichaza iphakheji yombane neyoluntu ekufuneka ilungiselelwe kwisiza.
| Umda wofakelo | ESSA0050B-0100 | ESSA0100B-0215 | Impembelelo kumthengi |
|---|---|---|---|
| Amandla ombane we-AC amiselweyo | Amashumi amahlanu eekhilowathi | I-100 kW | I-ESSA100 igalela umsantsa we-75 kW. |
| Umbane oqhubekayo oqikelelweyo | Amashumi asixhenxe anesibini A | Ikhulu namashumi amane anesine A | Utshintsho lwezinga lefeeder nesixhobo sokukhusela |
| Amandla ebhetri alinganisiweyo | I-100.352 kWh | 215.04 kWh | I-ESSA100 ifikelela kudidi lwamandla olufunekayo. |
| Imilinganiselo, Ububanzi × Ubunzulu × Ukuphakama | 1,770 × 1,510 × 2,270 mm | 2,450 × 1,550 × 2,400 mm | I-ESSA100 idinga isikhundla sesixhobo esikhulu. |
| Ubunzima | 2,400 kg | Ii-kilogram ezingama-3,900 | Isiseko nesicwangciso sokuphatha kufuneka zikwazi ukuthwala i-1,500 kg ngaphezulu. |
| Ukupholisa / Isingxobo | Ukupholisa umoya okubalulekileyo / IP54 | Ukupholisa umoya okubalulekileyo / IP54 | Iqondo lobushushu elingqongileyo kunye nokuhamba komoya zihlala ziyimingeniso eyamkelekileyo. |
I- Uqhagamshelo lweswitshibhodi olukhoyo lwe-400 V Kufuneka kuhlolwe umbane oqhubekayo, ulungelelwaniso lokhuseleko, inqanaba lophazamiseko, ukwahlula kunye nendlela yomtya. I-transformer yokwahlula eyakhelweyo yinzuzo yodibaniso lweMegSolid, kodwa ayisusi imfuneko yokuqinisekisa uyilo olupheleleyo lokhuseleko lwendawo.
Cwangcisa ukuzalisa amandla phambi kokuvuna okulandelayo okanye umsitho wangokuhlwa.
Ukunciphisa incopho kunokuphindaphindeka ngokuthembekileyo kuphela xa ikhabhinethi iqala isiganeko ngasinye inamandla aneleyo asetyenziswayo. Emva kokuhambisa i-136.25 kWh AC, inkqubo kufuneka ifumane ngaphezulu kwe-136.25 kWh kwindawo yayo yokutshaja kuba iilahleko zoguqulo kunye nezixhobo zokuncedisa zisebenzisa inxalenye yamandla angenayo.
Vumelana nokuzihlaziya nomcimbi olandelayo
Indawo yokwenza iwayini kufuneka ithelekise iirekhodi ezintathu ezihambelana nexesha:
- Intsalela ye-PV ekhoyo phambi kwesiganeko esilandelayo;
- Indawo evumelekileyo yokungenisa umbane kwigridi ngexesha lokutshaja;
- I-SOC yebhetri elinganisiweyo kunye namandla e-AC e-BESS angokoqobo.
Imisebenzi kaMegSolid yokuqikelela umthamo webhetri nexesha lokukhupha ibhetri iyayixhasa loo sicwangciso sokusebenza. Uvavanyo lwamandla e-AC asebenzisekayo Kufuneka ke kuqinisekiswe ukuba i-ESSA0100B-0215 iyakwazi ukuhambisa ulandelelwano oluthembisiweyo phantsi kweemeko zokushisa zendawo, i-SOC kunye namandla.
Ikhabhathi kufuneka iqale isiganeko esilandelayo inamandla aneleyo asebenzisekayo ukuze iphinde umthwalo wokulawula umphakamo we-75 kW kunye noluhlu olupheleleyo lwemveliso. Ngaphandle kokutshajwa ngokwaneleyo phambi kwesiganeko esilandelayo, ikhabhathi ayinakuyiphinda loo ncedo nokuba ubukhulu bayo bubonisiwe kangakanani na.
Faka iSistim yeMegSolid encinci okanye enkulu kuphela kumda ochanekileyo.
Gcina i-ESSA0050B-0100 ingaphantsi komda we-50 kW
I-MegSolid iyacebisa ESSA0050B-0100 xa ukuncipha okulinganisiweyo kokungenisa kungadluli kwi-50 kW kwaye amandla e-AC asetyenziswayo aqinisekisiweyo abandakanya isiganeko sonke. Loo mthwalo ungasebenzisa elincinane Amashumi asixhenxe anesibini A, 2,400 kg ikhabhathi ngaphandle kokuthwala amandla nomthamo wamandla ongeyomfuneko.
I-MegSolid iyacebisa ESSA0100B-0215 xa isikhewu sidlula i-50 kW, ulandelelwano lokusebenza ludlula i-window yamandla asetyenziswayo yekhabhathi encinci, okanye zombini ezi meko zenzeka. Indawo yokwenza iwayini ekuvavanyweyo idlula zombini ezi mida nge 75 kW kwaye 136.25 kWh AC, ngoko ke ikhabhathi ye-100 kW / 215.04 kWh yeyona nto ifanelekileyo ukuyithenga.
Yenyuka ngaphezu kwe-ESSA100 kuphela xa umthwalo olinganisiweyo ukufuna njalo
Iiprojekthi ezingaphezulu kwe-100 kW okanye ezingenakungena kwi-window yamandla asetyenzisiweyo efunekayo ngaphakathi kwi-ESSA100 zidinga isakhiwo esikhulu. EzikaMegSolid 261.24 kWh iqonga le-Energon inikezela ngokwahlukileyo 125 kVA Udidi lweemveliso ezipholiswa lulwelo; i-125 kVA akufuneki ithathwe njenge-125 kW ngokuzenzekelayo. Iikampasi ezinkulu zeewinery kufuneka zingenele eso siphononongo sobunjineli phambi kokuba iimpahla zomyalo.
Chaza i-ESSA0100B-0215 kumthwalo we-AC we-75 kW ne-136.25 kWh.
Imida emibini elinganisiweyo imisela udidi lwezixhobo. ESSA0050B-0100 ayifikeleli kwinjongo yokungenisa nge 25 kW kwaye amandla ebhetri ayo aqikelelweyo 35.898 kWh ngaphantsi umthwalo we-AC ofunekayo phambi kokulahleka. ESSA0100B-0215 ibonelela ngokuchanekileyo Udidi lwe-AC olulinganiselwe kwi-100 kW kwaye Uklasi wamandla avavanyiweyo we-215.04 kWh kwikhabhathi enye yangaphandle.
I-ESSA0100B-0215 ingavavanywa ngokumelene nomthwalo opheleleyo wokuvuna, iphinde isetyenziswe kutshintsho lwelanga olungeyokuvuna kwaye idityaniswe nolawulo lokungathumeli kumaza ngaphandle ngokusebenzisa imida ecacisiweyo ye-EMS kunye nonxibelelwano. Uqhagamshelo lwayo lwe-400 V, 144 A kunye nomthwalo wofakelo we-3,900 kg ziyaziwa phambi kokuba kuthengwe, ukuze umsebenzi wombane nowokwakha usetyenzwe ngokwe-cabinet kanye.
Imibuzo Ebuzwa Rhoqo
Yeyiphi ibhetri yeMegSolid ecetyiswayo kwindawo yokwenza iwayini yaseSpain enesikhewu esiphezulu esiyi-75 kW?
IMegSolid icebisa i-ESSA0100B-0215. Amandla ayo e-AC aqikelelwe kwi-100 kW agqitha isikhewu esilinganisiweyo se-75 kW, ngelixa i-ESSA0050B-0100 ye-50 kW isaphulukene nge-25 kW.
Kutheni i-ESSA0100B-0215 ingcono kumsebenzi we-AC we-136.25 kWh?
Amandla ebhetri ayo alinganiselwe kwi-215.04 kWh anika udidi lwamandla olufanelekileyo kulandelelwano olupheleleyo. Umlinganiselo we-100.352 kWh wekhabhathi encinci sele ungaphantsi nge-35.898 kWh kunomthwalo we-AC ofunekayo phambi kokulahleka kwamandla.
I-ESSA0050B-0100 ingcono nini njengeprodukthi yeMegSolid?
Kuyilinganelo eyomeleleyo xa ukuncitshiswa komthamo olinganisiweyo kuhlala kungaphakathi kwi-50 kW kwaye isiganeko esipheleleyo singena kwi-window yamandla e-AC asetyenziswayo aqinisekisiweyo.
Ingaba i-array ye-PV eyi-100 kWp ifuna i-BESS eyi-100 kW?
Hayi. Amandla e-BESS alandela ukunqongophala kokungenisa okulinganisiweyo kunye nomda wokutshaja. Amandla e-BESS alandela i-window yokukhupha, isisele samandla elanga esinokusetyenziswa kunye negcini ye-SOC efunekayo.
Ingaba amandla ebhetri alinganisiweyo anokuphathwa njengamandla e-AC asebenzisekayo?
Hayi. Amandla e-AC ahanjiswayo axhomekeke kwifestile ye-SOC evunyelwene ngayo, ilahleko yoguqulo, imithwalo encedisayo, ubushushu kunye namandla okukhupha. Ukuqaliswa komsebenzi kufuneka kuqinisekise umda we-AC.
Ingakwazi i-ESSA0100B-0215 ukuxhasa i-solar esele ikhona kwindawo yokwenza iwayini?
Ewe, uyilo oludityaniswe nge-AC lunokugcina izixhobo ze-PV ezikhoyo ezifanelekileyo xa ibhodi yokutshintshela, ukhuseleko, iimitha kunye nezilawuli zixhasa olu lungelelwaniso.
Ingaba ikhabhinethi ye-ESSA imisela ukuba kungabikho nto ithunyelwa ngaphandle ngokwayo?
Hayi. Ikhabhathi ibonelela nge-EMS kunye nemisebenzi yonxibelelwano, ngelixa imitha ye-PCC, isilawuli sendawo, i-PV inverter, kunye nenkqubo yokhuseleko neyokuthintela ukuthunyelwa ngaphandle kufuneka zidlula kuvavanyo lwendawo olulungelelanisiweyo.
I-ESSA0100B-0215 ibonelela ngohlobo luni lwesiphelo sombane?
I-MegSolid ipapasha ujongano lwe-AC olulinganiselwe kwi-400 V kunye nomsinga we-AC olinganiselwe kwi-144 A kwi-ESSA0100B-0215. Uyilo lwebhodi yokutshintshela kunye nokhuseleko olukhoyo kufuneka luqinisekiswe kuloo mida.
Ingaba i-ESSA0100B-0215 ipholiswa ngulwelo?
Hayi. I-MegSolid ichaza ukupholisa komoya okukrelekrele kwi-ESSA0100B-0215. Inkqubo ye-Energon eyi-261.24 kWh iklasi yemveliso eyahlukileyo epholiswa ngulwelo.
I-ESSA0100B-0215 inkulu kwaye inzima kangakanani?
Imilinganiselo yayo epapashiweyo yi-2,450 × 1,550 × 2,400 mm, nobunzima bayo obupapashiweyo yi-3,900 kg.
Indawo yokwenza iwayini iyivuselela njani amandla phambi kwesipikokazi sesibini?
I-EMS isebenzisa intsalela ye-PV ekhoyo okanye indawo evumelekileyo yokungenisa umbane kwinethiwekhi, ngelixa igcina imida yokungenisa nokuthumela umbane. Ukuhambelana kwamandla e-SOC, e-PCC, umveliso we-PV kunye namandla e-BESS kuqinisekisa ukuba ixesha lokutshaja kwakhona liyavala na.
Zeziphi iimigaqo zaseSpain ezichaphazela i-BESS yewayini engathumeli phesheya?
I-Real Decreto 244/2019 ichaza ukuzisebenzisa ngaphandle kokuseleyo, kwaye i-ITC-BT-40 elungisiweyo imisela iimfuno novavanyo lwesixhobo esithintela ukuthunyelwa kumraro wokusasaza.
Yeyiphi inzuzo iMegSolid ESSA100 eyinika indawo yokwenza iwayini?
Ihlangabezana neemfuno zamandla achaziweyo angama-75 kW kwaye ibonelela ngeklasi yamandla alinganisiweyo engama-215.04 kWh efunekayo ukuvavanya ulandelelwano olupheleleyo lwe-AC olungama-136.25 kWh, ngelixa idibanisa imisebenzi ye-EMS, unxibelelwano kunye netransformer yokwahlula kwiqonga elinye langaphandle.